Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sw_position | 40FE | SW position | Setting the switch position enables the display orientation to be kept fixed, regardless of in which direction relative to the piping the converter is installed. | R/W | Enum | 2048 |
input_range_type | 4015 | Type | SINGLE:Single range. 4F-0R:Unidirectional flow, automatic selection of multiple ranges. 2F-2R:Bidirectional flows, automatic selection of multiple ranges. EXT 2F-0R:Unidirectional flow, multiple ranges selected by external signal. EXT 2F-2R:Bidirectional flows, multiple ranges selected by external signal. | R/W | Enum | 32 |
input_range_units | 400F | Unit | Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value | R/W | Enum | 32 |
input_upper_value | 4010 | Range1 | Range1 span value. Range can be set within 0.1m/s to 10m/s in terms of flow velocity. | R/W | Float | 32 |
input_upper_value2 | 4011 | Range2 | Range2 span value. | R/W | Float | 32 |
input_upper_value3 | 4012 | Range3 | Range3 span value. | R/W | Float | 32 |
input_upper_value4 | 4013 | Range4 | Range4 span value. | R/W | Float | 32 |
input_multi_range_hysteresys | 4016 | Range hys | Range hysteresis is the dead band used when multiple ranges are switched. You can set the hysteresis within the range of 0 to 25% in increments of 0.1%. | R/W | Unsigned | 4 |
fixed_pulse | 40FF | Fixed pulse | R/W | Unsigned | 32 | |
fixed_current | 4100 | Fixed current | R/W | Float | 32 | |
Name | ID | Label | Description | Type | Access | Class |