Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
FlowMinimumSpan | 40EA | Minimum span | R | Float | 0 | |
pressureValue | 40EB | Pres | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 10 |
pressureUnits | 40EC | Pressure unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. Pressure- Pressure of the process measured with respect to a reference pressure | R/W | Enum | 0 |
pressureUSL | 40ED | Pres USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 0 |
pressureLSL | 40EE | Pres LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 0 |
pressureMinimumSpan | 40EF | Pres min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 0 |
pressureDampingValue | 40F0 | Damping | Damping value is used to moderate output fluctuations. The larger damping value, the more the output is averaged. But the response to an input change will be slower.Damping value is set for 0.0sec, 0.5sec and 1 to 60sec (in increments of 1sec). | R/W | Float | 0 |
pressureSerialNumber | 40F1 | Pres snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
input_calibration_mode | 4027 | Calibration Mode | W | Unsigned | 32 | |
input_calibration_step | 4028 | Calibration Step | W | Unsigned | 32 | |
Name | ID | Label | Description | Type | Access | Class |