Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
FlowValue | 40E0 | Flow | Расход | R | Float | 10 |
FlowUnits | 40E1 | Flow unit | Единица расхода | R/W | Enum | 0 |
FoValue | 40E2 | FO | Forward flow direction total value | R | Float | 10 |
RvValue | 40E3 | RV | Reverse flow direction total value | R | Float | 10 |
DfValue | 40E4 | DF | Difference between forward and reverse total value | R | Float | 10 |
TotalUnits | 40E5 | Unit | Total flow unit | R/W | Enum | 0 |
input_percent_value | 40E6 | Percent | Процент диапазона - переменная, которая отслеживает представление цифрового значение по отношению к диапазону, заданному значениями 'Значение нижнего предела диапазона' и 'Значение верхнего предела диапазона', для обычных рабочих режимов. Единицы этой переменной всегда выражены в процентах. | R | Float | 10 |
FlowLUnits | 40E7 | Limit unit | R | Enum | 0 | |
FlowUSL | 40E8 | Upper sensor limit | R | Float | 0 | |
FlowLSL | 40E9 | Lower sensor limit | R | Float | 0 | |
FlowMinimumSpan | 40EA | Minimum span | R | Float | 0 | |
pressureValue | 40EB | Давл | Значение переменной полевого устройства - это цифровое значение, которое меняется во времени без участия пользователя. Давление - давление процесса, измеренное по в сравнении с контрольным давлением. | R | Float | 10 |
pressureUnits | 40EC | Ед.изм. давления | Единицы измерения переменной полевого устройства - ед. измерения, которые должны отображаться с 'Числовым значением', 'Минимальным диапазоном', 'Значением верхнего предела диапазона', 'Значением нижнего предела диапазона', 'Нижним пределом сенсора' и 'Верхним пределом сенсора'. Давление - давление процесса, измеренное по отношению к контрольному давлению. | R/W | Enum | 0 |
pressureUSL | 40ED | USL давл | Значение верхнего предела сенсора - определяет максимально возможное значение для верхнего предела диапазона. Давление - давление процесса, измеренное по отношению к контрольному давлению. | R | Float | 0 |
pressureLSL | 40EE | LSL давл | Значение нижнего предела сенсора - определяет минимально допустимое значение для нижнего предела диапазона. Давление - давление процесса, измеренное по отношению к контрольному давлению. | R | Float | 0 |
pressureMinimumSpan | 40EF | Мин диап давл | Значение минимального диапазона - определяет наименьшую допустимую разницу между значениями верхнего и нижнего пределов диапазона. Давление - давление процесса, измеренное по отношению к контрольному давлению. | R | Float | 0 |
pressureDampingValue | 40F0 | Damping | Damping value is used to moderate output fluctuations. The larger damping value, the more the output is averaged. But the response to an input change will be slower.Damping value is set for 0.0sec, 0.5sec and 1 to 60sec (in increments of 1sec). | R/W | Float | 0 |
pressureSerialNumber | 40F1 | Сер.ном. сенс давл. | Серийный номер сенсора - служит уникальным идентификатором сенсора, по которому в первую очередь выводится представление цифрового значения или переменная полевого устройства | R | Unsigned | 2048 |
input_calibration_mode | 4027 | Calibration Mode | W | Unsigned | 32 | |
input_calibration_step | 4028 | Calibration Step | W | Unsigned | 32 | |
input_excitation_current | 4030 | Exc Curr Dsp | R | Float | 4 | |
input_low_cut_value | 400E | Low cut | Low cutoff is the function to set the current output to zero forcefully if the flow rate is equal to or less than the low cutoff value set near 0%. Low cutoff value can be set within the range 0 to 10% in increments of 0.1%. | R/W | Float | 32 |
input_excitation_frequency_code | 401B | Exc freq | Since each exciting frequency value has its own characteristics, you should select an appropriate exciting frequency (24Hz is set at shipment. Depending on the characteristics of the detector, a large frequency may result in excitation failure. When a large frequency value is set and it changes the indicator value, decrease the frequency to a value that will not change the indicator value.) | R/W | Enum | 32 |
input_pulse_rate_unit | 4017 | Unit | Unit of count rate | R/W | Enum | 32 |
input_pulse_rate | 4018 | Count rate | R/W | Float | 32 | |
input_pulse_width | 4019 | Pulse width | R/W | Unsigned | 32 | |
input_pulse_mode | 40F2 | Pulse mode | AUTO:After the count rate is set, the pulse width is automatically set to 40% of the period of pulse frequency at 100% output. MANUAL:Even after the count rate is set, the pulse width is not changed. | R/W | Enum | 32 |
input_d_size | 401C | Meter size | R/W | Unsigned | 32 | |
input_d_size_unit | 40AA | Meter size unit | R/W | Enum | 32 | |
input_signal_status_code | 401F | Alarm set1 | R/W | BitEnum | 32 | |
input_signal_status_code2 | 40F3 | Alarm set2 | R/W | BitEnum | 32 | |
input_alarm_upper_value | 401D | High alarm | R/W | Integer | 32 | |
input_alarm_lower_value | 401E | Low alarm | R/W | Integer | 32 | |
input_empty_level | 40AB | Empty alarm level | R/W | Enum | 32 | |
input_alarm_upper_value2 | 40F4 | HH alarm | R/W | Integer | 32 | |
input_alarm_lower_value2 | 40F5 | LL alarm | R/W | Integer | 32 | |
input_signal_percent_rate_limit | 4020 | Rate-of-change limit | R/W | Unsigned | 32 | |
input_signal_time_rate_limit | 4021 | Control limit time | R/W | Unsigned | 32 | |
sensor_damping_value | 4009 | Damping | Damping value is used to moderate output fluctuations. The larger damping value, the more the output is averaged. But the response to an input change will be slower.Damping value is set for 0.0sec, 0.5sec and 1 to 60sec (in increments of 1sec). | R/W | Float | 8 |
detector_serial_number | 4023 | Detector | Detector's serial number | R | PackedAscii | 2048 |
converter_serial_number | 4024 | Converter | Converter's serial number | R | PackedAscii | 2048 |
detector_spec_code | 4090 | Detector | Detector's product specification code | R | PackedAscii | 2048 |
converter_spec_code | 4091 | Converter | Converter's product specification code | R | PackedAscii | 2048 |
input_ex_curr | 408D | Exc current | Be sure to match the exciting current value with the value specified for the combined detector. Specifying any other value may cause an error. The setting range of excitation current value is from 0.0000A to 0.2500A. | R/W | Float | 32 |
input_flange_types | 4092 | Flange type | R/W | Enum | 2048 | |
LF600_liner_material | 40F6 | Lining material | R/W | Enum | 2048 | |
LF600_electrode_material | 40F7 | Electrode material | R/W | Enum | 2048 | |
connection_flgn_matl | 402C | Earthring material | R/W | Enum | 2048 | |
seal_material | 4029 | Seal matl | R/W | Enum | 2048 | |
input_pass_word | 40B4 | Password | R/W | Unsigned | 32 | |
Name | ID | Label | Description | Type | Access | Class |