Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
hardware_revision | 009F | Hardware rev | Hardware Revision- Revision that corresponds to the electronics hardware of the Field Device. | R | Unsigned | 2048 |
physical_signaling_code | 00AB | Physicl signl code | Physical Signaling Code- The Physical Signaling Code describes the type of Physical Layer that has been implemented in the hardware that is responsible for the HART Communication port | R | Enum | 2048 |
device_flags | 00A0 | Dev flags | Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer | R | BitEnum | 128 |
device_id | 00A1 | Dev id | Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. | R | Unsigned | 128 |
polling_address | 00A2 | Poll addr | Polling Address- Address used by the Host to identify a Field Device, and changeable by the User to control: the Multidrop Mode for Analog Output 1), and the Analog Output Fixed Mode of Analog Output 1) | W | Unsigned | 128 |
tag | 00A3 | Tag | Tag- Text that is associated with the Field Device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label: a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. | R/W | PackedAscii | 2048 |
message | 00A4 | Message | Message- Text that is associated with the Field Device. This text can be used by the user in any way. There is no recommended use. | R/W | PackedAscii | 2048 |
descriptor | 00A5 | Descriptor | Descriptor- Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use. | R/W | PackedAscii | 2048 |
date | 00A6 | Date | Date- Gregorian calendar date that is stored in the Field Device. This date can be used by the user in any way. There is no specific recommended use. | R/W | HartDate | 2048 |
write_protect | 00A7 | Write protect | Write Protect Mode- Indicates whether variables can be written to the Field Device, or whether commands that cause actions, to be performed in the Field Device, can or cannot occur. Depending on the Field Device, this is a mode that is controllable by the user, either via the Field Device hardware or the HART Protocol. | R | Enum | 2048 |
private_label_distributor | 00A8 | Distributor | Private Label Distributor- References the company that is responsible for the distribution of this Field Device to customers | R | Enum | 2048 |
final_assembly_number | 00A9 | Final asmbly num | Final Assembly Number- Number that is used for identification purposes, and is associated with the overall Field Device. | R/W | Unsigned | 2048 |
xmtr_specific_status_0 | 0FB5 | Status group 1 | Field Device Specific Status Byte 1- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
xmtr_specific_status_1 | 0FB6 | Status group 2 | Field Device Specific Status Byte 2- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
xmtr_specific_status_2 | 0FB7 | Status group 3 | Field Device Specific Status Byte 3- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
xmtr_specific_status_3 | 0FB8 | Status group 4 | Field Device Specific Status Byte 4- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
flange_type | 139A | Flange type | Flange Type- Hardware, adjacent to the sensor, that physically connects the process to the sensor | R/W | Enum | 2048 |
o_ring_material | 139B | O ring matl | O Ring Material- Construction material of a seal that exists between the module and flange | R/W | Enum | 2048 |
meter_installation | 139C | Meter type | Meter Installation- Defines whether there is a meter installed or not and possibly what information the meter will display | R/W | Enum | 256 |
remote_seal_type | 139D | RS type | Remote Seal Type- Type of device that is capable of detecting and passing on the process pressure on to the module. This is only unambiguous if 1 remote seal is installed. | R/W | Enum | 2048 |
module_fill_fluid | 139E | Fill fluid | Sensor Fill Fluid- Fluid material in the module | R | Enum | 2048 |
number_of_remote_seals | 139F | Num remote seal | Number of Remote Seals- Physical quantity of the seals for the remote seal that is installed | R/W | Enum | 2048 |
sensor_a_lower_sensor_trim_point | 1774 | Pres snsr LST pt | Lower Sensor Trim Point- Applied process pressure at which the last low sensor trim was performed. Pressure Sensor- Pressure hardware that measures pressure with respect to a reference pressure. | R/W | Float | 8 |
sensor_a_upper_sensor_trim_point | 1776 | Pres snsr UST pt | Upper Sensor Trim Point- Applied process pressure at which the last upper sensor trim was performed. Pressure Sensor- Pressure hardware that measures pressure with respect to a reference pressure. | R/W | Float | 8 |
sensor_a_sensor_trim_unit | 1772 | Pres snsr ST unit | Sensor Trim Unit- Unit associated with the Sensor Lower Trim and Sensor Upper Trim. Pressure Sensor- Pressure hardware that measures pressure with respect to a reference pressure. | R | Enum | 8 |
analog_output_value | 1779 | AO1 Out | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes. Analog Output- Measurable physical output which changes with respect to time, without user intervention. | R/W | Float | 66 |
analog_output_alarm_select | 177A | AO1 Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. Analog Output- Measurable physical output which changes with respect to time, without user intervention. | R | Enum | 64 |
module_type_code | 177B | Meas typ | Measurement Type- Type of measurement application this Field Device is intended to be used with | R | Enum | 2048 |
flange_material | 177C | Flnge matl | Flange Material- Construction material of flange type | R/W | Enum | 2048 |
meter_information_configuration | 177D | Meter typ config | Meter Information Configuration- Defines what information the meter will display | R/W | Enum | 256 |
remote_seal_isolator_material | 177E | RS isoltr matl | Remote Seal Isolator Material- Construction material of a part of the remote seal type that comes in contact with the process material. This is only unambiguous if 1 remote seal is installed. | R/W | Enum | 2048 |
module_isolator_material | 177F | Isoltr matl | Sensor Isolator Material- Construction material of a part of the module type that comes in contact with the process material | R | Enum | 2048 |
drain_vent_material | 1780 | Drain vent matl | Drain Vent Material- Construction material of a removable plug that exists on the flange type that can be opened temporarily to remove unwanted process from the sensor area | R/W | Enum | 2048 |
Name | ID | Label | Description | Type | Access | Class |