Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sensor_value | 4001 | Pres | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R | Float | 10 |
sensor2_value | 4002 | TS | TS- Temperature of the sensor that is making the process measurement. | R | Float | 10 |
sensor3_value | 4003 | TC | TC- Temperature of the electronics that is responsible for the process measurements | R | Float | 10 |
sensor4_value | 4004 | PS | PS- Pressure of the process measured with respect to the reference pressure equal to 0. | R | Float | 10 |
sensor_units | 4000 | PV Snsr unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 8 |
sensor2_units | 4005 | PV Snsr unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R | Enum | 8 |
sensor3_units | 4006 | PV Snsr unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R | Enum | 8 |
sensor4_units | 4007 | PV Snsr unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R | Enum | 8 |
sensor_upper_limit | 4008 | PV USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
sensor_lower_limit | 4009 | PV LSL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
sensor_minimum_span | 400A | PV Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 8 |
sensor_damping_value | 400B | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 8 |
analog_value | 400C | AO1 | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes | R/W | Float | 66 |
analog_alarm_code | 400D | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
input_percent_range | 400E | PV % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
input_sift_percent_range | 400F | PV % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | W | Float | 4 |
input_transfer_function | 4010 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R/W | Enum | 32 |
input_low_cut_value | 4011 | Low cut value | R/W | Float | 32 | |
input_units | 4012 | PV rnge unit | Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value | R/W | Enum | 32 |
input_lower_value | 4013 | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
input_upper_value | 4014 | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
sensor_serial_number | 4015 | PV Snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 2048 |
transmitter_spec_code | 4016 | Spec code | Model spec code | R | PackedAscii | 2048 |
transmitter_ser_no | 4017 | Serial number | Transmitter full serial number | R | PackedAscii | 2048 |
remote_seal_fill_fluid | 4018 | RS fill fluid | Remote Seal Fill Fluid- Fluid material in the device remote seal. | R/W | Enum | 2048 |
module_range_code | 4019 | Module rnge | Module range number- pressure range number located on the side of the sensor | R/W | Enum | 2048 |
unique_device_type_code | 07ED | R/W | Enum | 4096 | ||
rosemount_model_code | 07F5 | R/W | Enum | 4096 | ||
rosemount_analytical_model_code | 07F6 | R/W | Enum | 4096 | ||
kayray_model_code | 07F7 | R/W | Enum | 4096 | ||
micro_motion_model_code | 07F8 | R/W | Enum | 4096 | ||
units_code | 07E9 | R/W | Enum | 4096 | ||
material_code | 07EC | R/W | Enum | 4096 | ||
alarm_selection_code | 07EB | R/W | Enum | 4096 | ||
write_protect_code | 07EE | R/W | Enum | 4096 | ||
company_identification_code | 07EF | R/W | Enum | 4096 | ||
burst_mode_control_code | 07F0 | R/W | Enum | 4096 | ||
physical_signaling_codes | 07F1 | R/W | Enum | 4096 | ||
flag_assignment | 07F2 | R/W | Enum | 4096 | ||
operating_mode_code | 07F3 | R/W | Enum | 4096 | ||
analog_output_numbers_code | 07F4 | R/W | Enum | 4096 | ||
response_code | 0096 | Command Specific Response Code- Data that is returned in the Field Device response, that indicates the relative success of the Command sent in the Host request. This information may relate to the Data of the Host request or to the command itself. | R/W | Enum | 129 | |
comm_status | 0098 | Communications Error Summary- The Field Device has detected the following error condition while attempting to receive the Host request. Therefore the Command was not accepted, and the Host request caused no change to occur in the Field Device. | R/W | BitEnum | 131 | |
device_status | 0097 | Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process | R/W | BitEnum | 131 | |
manufacturer_id | 0099 | Manufacturer | Manufacturer Identification Code- References a specific manufacturer, which is usually a company name, that is responsible for the manufacture of this Field Device. | R | Enum | 128 |
device_type | 009A | Model | Model- References the type of Field Device, usually an advertised model number, that is unique to a single manufacturer | R | Enum | 128 |
request_preambles | 009B | Num req preams | Number of Request Preambles- Number of Preambles required from the Host request by the Field Device | R | Unsigned | 128 |
universal_revision | 009C | Universal rev | Universal Revision- Revision of the Universal Device Description, that the Field Device conforms to | R | Unsigned | 128 |
transmitter_revision | 009D | Fld dev rev | Field Device Revision- Revision of the Field Device Specific Device Description, that the Field Device conforms to | R | Unsigned | 128 |
software_revision | 009E | Software rev | Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the Field Device | R | Unsigned | 2048 |
Name | ID | Label | Description | Type | Access | Class |