PressureMaximumUTP 4064 Pres Max upper trim Maximum Upper Trim Point- The highest applied process value that can be used duirng a high trim procedure (ie, no value higher than this will be accepted by the instrument). R Float 0
PressureMinimumTrimDiff 4065 Pres Min trim diff Minimum Trim Differential- The minimum acceptable difference between the upper and lower trim points. R Float 0
PressureSimulated 4066 Simulate W Enum 2052
Pressure_upperRange_value 4067 PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
Pressure_lowerRange_value 4068 PV LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
PressureCalStatus 4069 Cal Status Presure Input Calibration Status R/W Enum 2048
PressureCalCount 406A Cal. Index Counter Pressure Input Calibration Index Count R Unsigned 2048
PressureCalEUZO_value 406B EU ZO Val Pressure Cal. Pt #1 EU Zero Value R/W Float 2048
PressureCalRawZO_value 406C Raw ZO Val Pressure Cal. Pt #1 Raw Zero Value R/W Float 2048
PressureCalEUMid_value 406D EU Mid Val Pressure Cal. Pt #2 EU Mid Value R/W Float 2048