Loading…
Name ID Label Description Type Access Class
QVloopCurrentUpperEndPoint 2F0B AO hi end pt Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
QVloopCurrentLowerEndPoint 2F0C AO lo end pt Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
QVloopCurrentUpperLimit 2F0D Upper Limit Value The maximum value of the analog signal. R Float 64
QVloopCurrentLowerLimit 2F0E Lower Limit Value The minimum value of the analog signal. R Float 64
QVpercentRange 2F0F QV % range Percent of range of the HART Quaternary Variable (QV); tracks the associated measured value with respect to the Lower Range Value and Upper Range Value. R Float 34
QVupperRange_value 2F11 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
QVlowerRange_value 2F12 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
eOptionOnlineMode 40DB Online Mode? Can the Host Application currently communicate with the field device? R/W Enum 4096
eOptionValidityDebug 40DC Show parameters Select: Show always all parameters or only those actually valid. For debugging purposes only. R/W Enum 4096
st16VersionDd 40DE DD-Version Version number of the device description according to NAMUR recommendation. You are currently working with version: 01.12 R/W ASCII 4096
Name ID Label Description Type Access Class