Loading…
Name ID Label Description Type Access Class
compat_burst_vars_7_1 410A Burst Variable Code Burst Variable Slot - Device variable code assigned to the slot to be read in burst mode. R/W Index 2048
compat_update_per_1 40FC Update Period Update period for the burst message in seconds when the burst trigger conditions are met. Allowed Values: 0.5, 1, 2, 4, 8, 16, 32, 60-3600. R/W Time 2048
compat_max_update_per_1 40FD Max Update Period Update period for the burst message in seconds when the burst trigger conditions are not met. Allowed Values: 0.5, 1, 2, 4, 8, 16, 32, 60-3600. R/W Time 2048
compat_burst_cmd_1 40FB Command Command message that is transmitted for the respective burst message by the device while in burst mode. R/W Enum 128
compat_burst_trig_level_1 4102 Burst Trigger Level The Burst Trigger level defines the threshold that must be exceeded to start bursting. R/W Float 2048
compat_burst_mode_1 40FE Burst mode Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. R/W Enum 128
compat_burst_trig_mode_1 40FF Trigger Mode Selects the Burst Trigger Mode. Burst messages may be configured to publish continuously or based on a Trigger Level. R/W Enum 128
compat_burst_trig_class_1 4100 Classification The classification of the burst trigger variable R/W Enum 16
compat_burst_trig_units_1 4101 Unit The unit of the burst trigger variable R/W Enum 16
compat_burst_vars_0_2 4116 Burst Variable Code Burst Variable Slot - Device variable code assigned to the slot to be read in burst mode. R/W Index 2048
Name ID Label Description Type Access Class