Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
device_specific_status_5 | 1030 | Status Group 5 | Field Device Specific Status Byte 6- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
loopCurrent | 00ED | Loop current | Loop Current- Loop current value as perceived by the device. | R/W | Float | 66 |
loop_alarm_code | 00EC | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
loop_flags | 00E7 | Channel flags | Analog Channel Flags- Defines the characteristics of the Analog Channel | R | BitEnum | 64 |
percentRange | 00E9 | PV % rnge | Percent of range; percental representation of the associated measured value with respect to the Lower Range Value and Upper Range Value. | R | Float | 34 |
transfer_function | 1F84 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |
upperRange_value | 00EA | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
lowerRange_value | 00EB | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
primary_variable_code | 0FD0 | PV is | Primary Index into the Dynamic Variables Array. Indicates which process value is mapped into the HART Primary Variable (PV). Equivalent to the process value of the of the current output. (Fct. C2.1.1/C3.1.4.1) | R/W | Index | 128 |
secondary_variable_code | 0FD1 | SV is | Secondary Index into the Dynamic Variables Array. Indicates which process value is mapped into the HART Secondary Variable (SV). Equivalent to the process value of the frequency output if available. (Fct. C2.2.3.1/C3.1.4.2) | R/W | Index | 128 |
Name | ID | Label | Description | Type | Access | Class |