Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
analog_channel_fixed1 | 1040 | AO fixed | Field Device Specific Dynamic Variable Analog Output Fixed- Data that indicates which of the Analog Outputs are, or are not, Fixed. The analog and digital Analog Outputs for the Dynamic Variable are held at a constant value (depending on the Mode of the Field Device). They will not respond to the applied process. | R | BitEnum | 2051 |
analog_channel_saturated_codes | 08D6 | R/W | Enum | 4096 | ||
analog_channel_fixed_codes | 08D7 | R/W | Enum | 4096 | ||
lock_device_code | 106F | Lock dev code | Lock Device Code- Indicates whether the device has been placed in a locked position to prevent any changes from being made manually or from another master. | W | Enum | 2048 |
lock_device_status_code | 1070 | Lock dev status | Lock Device Code- Indicates whether the device has been placed in a locked position to prevent any changes from being made manually or from another master. | R | BitEnum | 2048 |
loopCurrent | 00ED | Loop current | Loop Current- Loop current value as perceived by the device. | R/W | Float | 66 |
loop_alarm_code | 00EC | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
loop_flags | 00E7 | Channel flags | Analog Channel Flags- Defines the characteristics of the Analog Channel | R | BitEnum | 64 |
percentRange | 00E9 | PV % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
transfer_function | 1F84 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |