Loading…
Name ID Label Description Type Access Class
analog_channel_fixed1 1040 AO fixed Field Device Specific Dynamic Variable Analog Output Fixed- Data that indicates which of the Analog Outputs are, or are not, Fixed. The analog and digital Analog Outputs for the Dynamic Variable are held at a constant value (depending on the Mode of the Field Device). They will not respond to the applied process. R BitEnum 2051
analog_channel_saturated_codes 08D6 R/W Enum 4096
analog_channel_fixed_codes 08D7 R/W Enum 4096
lock_device_code 106F Lock dev code Lock Device Code- Indicates whether the device has been placed in a locked position to prevent any changes from being made manually or from another master. W Enum 2048
lock_device_status_code 1070 Lock dev status Lock Device Code- Indicates whether the device has been placed in a locked position to prevent any changes from being made manually or from another master. R BitEnum 2048
loopCurrent 00ED Loop current Loop Current- Loop current value as perceived by the device. R/W Float 66
loop_alarm_code 00EC AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
loop_flags 00E7 Channel flags Analog Channel Flags- Defines the characteristics of the Analog Channel R BitEnum 64
percentRange 00E9 PV % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
transfer_function 1F84 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R Enum 32
Name ID Label Description Type Access Class