Name ID Label Description Type Access Class
sensor_value 4000 PV Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention R/W Float 10
sensor_units 4001 PV Snsr unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 2050
sensorfamily 4002 PV Sensor fmly Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. R Enum 2048
sensor_upper_limit 4003 PV USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 2050
sensor_lower_limit 4004 PV LSL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 2050
sensor_minimum_span 4005 PV Min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 2050
sensor_damping_value 4006 PV Damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 2050
sensor_classification_code 4007 PV Class Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. R Enum 0
sensor_serial_number 4008 PV Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R Unsigned 2048
sensorPDQ 4009 PV Sensor PDQ Process Data Quality- Indicates the overall process data quality of the device variable value. R/W Enum 2050
sensorLS 400A PV Sensor LS Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). R/W Enum 2050
sensorStatus 400B PV Sensor Stat Device Family Status- Indicates additional status information on a device variable for a specific device family. R/W BitEnum 2050
sensorSimulated 400C Simulate W Enum 2052
total_value 400D Flow Total Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention R/W Float 10
total_unit_code 400E Flow Total Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 2050
totalfamily 400F total fmly Device Family- Indicates the family (i.e, pressure, temperature, flow, etc.) that the device variable belongs. R Enum 2048
total_upper_limit 4010 SV Usl Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 2050
total_lower_limit 4011 SV Lsl Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 2050
total_minimum_span 4012 sv minimum span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 2048
total_damping_value 4013 sv damping value Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 2048
total_classification_code 4014 SV Class Classification- Indicates the unit code expansion table used for a particular dynamic or device variable. R Enum 0
total_serial_number 4015 sv serial number Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R Unsigned 2048
totalPDQ 4016 SV PDQ Process Data Quality- Indicates the overall process data quality of the device variable value. R/W Enum 2050
totalLS 4017 SV LS Limit Status- Indicates whether the device variable is limited (i.e., not responding to a process). R/W Enum 2050
totalStatus 4018 SV Stat Device Family Status- Indicates additional status information on a device variable for a specific device family. R/W BitEnum 2050
totalSimulated 4019 Simulate W Enum 2052
temperature_unit 401E Temperature Unit R Enum 2048
temperature_value 401F Internal Temperature R Float 2050
temperature_variable_status 4020 Temperature Variable Status R Unsigned 2050
enable_disable_code 4021 Enable Disable Code R/W Enum 34
lower_value 4022 Lower Value R/W Float 34
higher_value 4023 Higher Value R/W Float 34
alarm_selection 4024 Alarm Selection R/W Enum 2050
operating_mode 402A Operating Mode R/W Enum 34
scaling_factor 402B Scaling Factor R/W Float 34
pulse_width_code 402C Pulse Width R/W Enum 34
pulse_unit_ratio 402D Pulse/Unit Ratio R/W Float 34
pv_safe_value 402E Flow Rate Safe Value R/W Float 34
fail_safe_behavior_code 402F Fail Safe Behavior R/W Enum 34
flow_rate_alarm_value_1 4032 Flow Rate Alarm Value R/W Float 34
flow_rate_hysteresis_1 4033 Hysteresis R/W Float 34
flow_total_alarm_value_1 4034 Flow Total Alarm Value R/W Float 34
alarm_type_code_1 4035 Alarm Type R/W Enum 34
contact_type_code_1 4036 Contact Type R/W Enum 34
function_1 4037 Function R/W Enum 34
do_operating_mode_1 403A DO Operating Mode 1 R Enum 34
do_output_1 403B DO Output 1 R Enum 34
do_operating_mode_2 403C DO Operating Mode 2 R Enum 34
do_output_2 403D DO Output 2 R Enum 34
flow_rate_alarm_value_2 4041 Flow Rate Alarm Value R/W Float 34