Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
ST_SensorOffset_1 | 4077 | Sensor offset 1 | Setting of the zero adjustment of the measured sensor value. | R/W | Float | 2048 |
ST_SensorConnection_1 | 4078 | Connection type 1 | Selection of of the sensor connection mode | R/W | Enum | 2048 |
ST_WireCompensation_1 | 4079 | 2-wire compensation 1 | Setting of the resistance for the 2-wire RTD compensation. | R/W | Float | 2048 |
ST_RjType_1 | 407A | Reference junction 1 | Selection of reference junction measurement for temperature compensation in thermocouples. | R/W | Enum | 2048 |
ST_FixedRjValue_1 | 407B | RJ preset value 1 | Setting of the value for the external temperature compensation. | R/W | Float | 2048 |
ST_CalVandusenA_1 | 407C | Call./v. Dusen coeff. A | Setting of the Callendar/van Dusen coefficient A for the linearization based on the Callendar-Van Dusen method. | R/W | Float | 2048 |
ST_CalVandusenB_1 | 407D | Call./v. Dusen coeff. B | Setting of the Callendar/van Dusen coefficient B for the linearization based on the Callendar-Van Dusen method. | R/W | Float | 2048 |
ST_CalVandusenC_1 | 407E | Call./v. Dusen coeff. C | Setting of the Callendar/van Dusen coefficient C for the linearization based on the Callendar-Van Dusen method. | R/W | Float | 2048 |
ST_CalVandusenR0_1 | 407F | Call./v. Dusen coeff. R0 | Setting of the R0 value for the linearization based on the Callendar-Van Dusen method. | R/W | Float | 2048 |
ST_PolyNickelCopperA_1 | 4080 | Polynomial coeff. A | Setting of the Polynomial coefficient A for Sensor linearization of copper/nickel resistance thermometers (RTD). | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |