Name ID Label Description Type Access Class
VOAT_KF_ramp_time 4869 Ramp Time Duration of ramp time. Total test time is then Init Time + 4 * Ramp Time + 2 * Steady Time. R Float 2050
VOAT_KF_test_hysteresis 486A Static Hysteresis During the steady time, the last 80 msec valve position is averaged in the opening ramp. The same average is calculated while closing the valve. The hysteresis is the difference of these values. R Float 2050
VOAT_KF_test_sensitivity 486B Sensitivity A percentage of change in input signal that is measured when the valve starts moving again after the steady state of the opening ramp is completed. R Float 2050
VOAT_KF_load_for_opening 486C Load for Opening The pressure difference (in bars) recorded when the valve starts to move from a closed position. R Float 2050
VOAT_KF_seat_load 486D Seat Load The absolute pressure difference in bars between the supply pressure (spring to open) or air pressure (spring to close) and the pressure at which the valve first closes. R Float 2050
VOAT_KF_SR_O2C_close 486E SR O2C Close Stroking Range Open to Close, Close. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. R Float 2050
VOAT_KF_SR_O2C_open 486F SR O2C Open Stroking Range Open to Close, Open. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. R Float 2050
VOAT_KF_SR_C2O_close 4870 SR C2O Close Stroking Range Close to Open, Close. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. R Float 2050
VOAT_KF_SR_C2O_open 4871 SR C2O Open Stroking Range Close to Open, Open. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. R Float 2050
test_data_index 4B52 Index to Test Data (0-9) 500 data points are stored in each test. This index refers always to 50 points: index 0 refers to points 0-49, index 9 refers to points 450-499. W Unsigned 2048
Name ID Label Description Type Access Class