Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
VOAT_KF_ramp_time | 4869 | Ramp Time | Duration of ramp time. Total test time is then Init Time + 4 * Ramp Time + 2 * Steady Time. | R | Float | 2050 |
VOAT_KF_test_hysteresis | 486A | Static Hysteresis | During the steady time, the last 80 msec valve position is averaged in the opening ramp. The same average is calculated while closing the valve. The hysteresis is the difference of these values. | R | Float | 2050 |
VOAT_KF_test_sensitivity | 486B | Sensitivity | A percentage of change in input signal that is measured when the valve starts moving again after the steady state of the opening ramp is completed. | R | Float | 2050 |
VOAT_KF_load_for_opening | 486C | Load for Opening | The pressure difference (in bars) recorded when the valve starts to move from a closed position. | R | Float | 2050 |
VOAT_KF_seat_load | 486D | Seat Load | The absolute pressure difference in bars between the supply pressure (spring to open) or air pressure (spring to close) and the pressure at which the valve first closes. | R | Float | 2050 |
VOAT_KF_SR_O2C_close | 486E | SR O2C Close | Stroking Range Open to Close, Close. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. | R | Float | 2050 |
VOAT_KF_SR_O2C_open | 486F | SR O2C Open | Stroking Range Open to Close, Open. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. | R | Float | 2050 |
VOAT_KF_SR_C2O_close | 4870 | SR C2O Close | Stroking Range Close to Open, Close. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. | R | Float | 2050 |
VOAT_KF_SR_C2O_open | 4871 | SR C2O Open | Stroking Range Close to Open, Open. The pressure required to stroke the valve assembly from the open position to the closed position and back to the open position with packing friction present but without flow or pressure. | R | Float | 2050 |
test_data_index | 4B52 | Index to Test Data (0-9) | 500 data points are stored in each test. This index refers always to 50 points: index 0 refers to points 0-49, index 9 refers to points 450-499. | W | Unsigned | 2048 |
Name | ID | Label | Description | Type | Access | Class |