Name ID Label Description Type Access Class
valve_test_number 4B4A Nbr of Test to Run Defines which valve test is started or cancelled. 0=Multipoint Step Test, 1=Dynamic Loop Test, 2=Valve Deadband Test, 3=Valve Analysis Test. W Enum 2048
valve_test_control 4B4B Start/Cancel Test Starts (1) or cancels (0) valve tests. W Enum 2048
number_of_points 4B4C Number of Steps in Multipoint Step Test Number of steps in Multipoint Step test. Must be in range 1-10. W Unsigned 2048
MPST_KF_starting_point 4858 Start Position Starting position of the valve as given in parameters. R Float 2050
MPST_KF_ending_point 4859 End Position Ending position of the valve as given in parameters. R Float 2050
MPST_KF_testing_time 485A Testing Time The total time for the test. R Float 2050
MPST_KF_td 485B Dead Time Td The time that the valve requires to move at least 0.005% after the input signal change has occured. R Float 2050
MPST_KF_t86 485C Step Response Time T86 The time elapsed when the valve reaches 86.5% of the realized step size (not the nominal stepwise change in the setpoint) R Float 2050
MPST_KF_overshoot 485D Overshoot The size of overshoot in percentage of the realised step. R Float 2050
MPST_KF_gain 485E Travel Gain The ratio between the step size of the control signal and the position measurement. In an optimum case, Travel Gain is 1.0. R Float 2050