Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
DLT_ramp_time | 4B3E | Ramp Time | Duration of ramp time. The total test time will be init time + 2 * ramp time. Default = 100.0s. | W | Float | 2048 |
DLT_init_time | 4B3F | Init Time | The time given to valve to reach the starting point of the loop test. Default = 10.0s. | W | Float | 2048 |
local_DLT_starting_point | 49D0 | Start Position | Start setpoint for the test. Default = 0.0%. | W | Float | 4096 |
local_DLT_ending_point | 49D1 | End Position | End setpoint for the test. The end setpoint may be smaller than start setpoint. In this case loop runs downwards in time. Default = 100.0%. | W | Float | 4096 |
local_DLT_ramp_time | 49D3 | Ramp Time | Duration of ramp time. The total test time will be init time + 2 * ramp time. Default = 100.0s. | W | Float | 4096 |
local_DLT_init_time | 49D2 | Init Time | The time given to valve to reach the starting point of the loop test. Default = 10.0s. | W | Float | 4096 |
VDT_starting_point | 4B41 | Start Position | Starting valve position for the valve deadband test. Valid values: Min. = 10.0%, max. = 90.0% Default = 5.0s. | W | Float | 2048 |
VDT_time_between_steps | 4B42 | Step Wait Time | The time to wait between successive 0.1% steps. The total test time can not be estimated. The absolute maximum is 40 * test_time. Valid values: Min. = 1.0s, max. = 20s Default = 5.0s. | W | Float | 2048 |
VDT_init_time | 4B43 | Init Time | The time given to valve to reach the starting point of the valve deadband test. Valid values: Min. = 0.0s, max. = 120s Default = 10.0s. | W | Float | 2048 |
local_VDT_starting_point | 4A66 | Start Position | Starting valve position for the valve deadband test. Valid values: Min. = 10.0%, max. = 90.0% Default = 5.0s. | W | Float | 4096 |
Name | ID | Label | Description | Type | Access | Class |