Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
DAC_board_HW_rev | 4038 | HART Board HW revision | DAC board hardware revision. | R | ASCII | 2048 |
DAC_board_SW_rev | 4039 | HART Board Dac SW revision | DAC board software revision. | R | ASCII | 2048 |
cal_current_select | 4B34 | 4 or 20 mA Select | Selection parameter in mA-calibration. | R/W | Unsigned | 2048 |
MPST_data_point_number | 4B36 | Number of Data Points | Number of steps in multi-point step test (max. = 10). Key figures are calculated only from the first step. | W | Unsigned | 2048 |
MPST_starting_point | 4B37 | Start Position | Starting position of the valve. Default = 50.0%. | W | Float | 2048 |
MPST_ending_point | 4B38 | End Position | Ending position of the valve. Default = 60.0%. | W | Float | 2048 |
MPST_step_time | 4B39 | Duration | The time between successive steps. The total test time = Init Time + Duration. Default = 8.0s. | W | Float | 2048 |
MPST_init_time | 4B3A | Init Time | The time given to valve to reach the starting point. Default = 2.0s for the first step, then 0.0s. | W | Float | 2048 |
DLT_starting_point | 4B3C | Start Position | Start setpoint for the test. Default = 0.0%. | W | Float | 2048 |
DLT_ending_point | 4B3D | End Position | End setpoint for the test. The end setpoint may be smaller than start setpoint. In this case loop runs downwards in time. Default = 100.0%. | W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |