Name ID Label Description Type Access Class
stiction_low_alimit 47FB Stiction Low Limit Lower alarm limit for Stiction. You can use the Stiction value to estimate internal frictions in the control valve package: Increased stiction suggests an increase in internal friction, which can cause accuracy problems and ultimately prevent the valve from moving. Decreased stiction suggests a decrease in internal friction. This may indicate problems such as extensive wear or valve shaft break. R/W Float 2049
stiction_high_alimit 47FC Stiction High Limit Upper alarm limit for Stiction. You can use the Stiction value to estimate internal frictions in the control valve package: Increased stiction suggests an increase in internal friction, which can cause accuracy problems and ultimately prevent the valve from moving. Decreased stiction suggests a decrease in internal friction. This may indicate problems such as extensive wear or valve shaft break. R/W Float 2049
stiction_latch_number 47FD Stiction Latch Number The measurement must exceed either of the limits as many times as the latch number indicates. R/W Float 2049
load_for_open_low_alimit 47FF Load for Opening Low Limit Lower alarm limit for Load for Opening. You can use Load for Opening to estimate the following: ·Seat wear, especially in butterfly valves ·Medium crystallization in e.g. ball valves. The Load for Opening trend is updated whenever the valve is opened from a fully closed position. Like stiction, this trend is based on the pneumatics measurement. R/W Float 2049
load_for_open_high_alimit 4800 Load for Opening High Limit Upper alarm limit for Load for Opening. You can use Load for Opening to estimate the following: ·Seat wear, especially in butterfly valves ·Medium crystallization in e.g. ball valves. The Load for Opening trend is updated whenever the valve is opened from a fully closed position. Like stiction, this trend is based on the pneumatics measurement. R/W Float 2049
load_for_open_latch_number 4801 Load for Opening Latch Number The measurement must exceed either of the alarm limits as many times as the latch number indicates. R/W Float 2049
supply_pressure_low_alimit 401A Supply Pressure Low Limit Lower alarm limit for the supply pressure. R/W Float 2049
supply_pressure_high_alimit 401B Supply Pressure High Limit Upper alarm limit for the supply pressure. R/W Float 2049
supply_pressure_latch_time 401C Supply Pressure Latch Time Time value in seconds for the supply pressure alarms. The measurement must remain out of the limits for the time period indicated by the latch time value. R/W Float 2049
dev_temperature_low_alimit 401D Temperature Low Limit Lower alarm limit for the device temperature. R/W Float 2049
Name ID Label Description Type Access Class