Loading…
Name ID Label Description Type Access Class
valve_dead_angle 4004 Dead Angle (a0) Takes into account the dead angle of the ball valves. The entire signal range is then used for effective valve opening 90°-a0. Refer to device IMO for proper dead angle value for your valve type. Default=0% R/W Float 2048
bypass_signal_modifications 4006 Bypass signal modification Defines whether Signal Modification parameters are applied or not. Options for this parameter are: ·Yes: Signal modifications are discarded ·No: (Default) Signal modifications are applied to original setpoint, and the control module then follows the modified setpoint. R/W Enum 2048
use_limits 4AF9 Use Travel Limits (this parameter is not used anymore) R/W Enum 2048
valve_package_info 4AFC Valve Package Info User defined parameter for valve package information. R/W Unsigned 2048
process_application_info 4AFF Process Appl. Info User defined parameter for process application information. R/W Unsigned 2048
total_op_time_wlimit 4012 Total Operation Time Warning limit for the Total Operation Time counter. Exceeding this value will generate a warning. R/W Float 2049
valve_total_travel_wlimit 4013 Total Valve Travel Warning limit for the Valve Total Travel counter. Exceeding this value will generate a warning. R/W Float 2049
valve_reversals_wlimit 4014 Total Valve Reversals Warning limit for the Valve Reversals counter. Exceeding this value will generate a warning. R/W Unsigned 2049
actuator_total_travel_wlimit 4015 Total Actuator Travel Warning limit for the Actuator Total Travel counter. Exceeding this value will generate a warning. R/W Float 2049
actuator_reversals_wlimit 4016 Total Actuator Reversals Warning limit for the Actuator Reversals counter. Exceeding this value will generate a warning. R/W Unsigned 2049
Name ID Label Description Type Access Class