Name ID Label Description Type Access Class
cut_off_high 400D High Cut-Off When this value is exceeded, the valve is set to a 100% position. This, however, does not guarantee that the valve reaches 100%. If, for example, the value is 98%, controller input is set to 100% when input signal is over 98%. R/W Float 2048
setpoint_high_limit 4009 Valve Position Limit HIGH Maximum setpoint to the control module. If setpoint is higher than high limit, it is limited/cut to the high limit. R/W Float 2048
setpoint_low_limit 4008 Valve Position Limit LOW Minimum setpoint to the control module. If setpoint is lower than low limit, it is limited/cut to the low limit. R/W Float 2048
travel_rate_inc 400A Travel Rate OPEN Describes the percentage of change per second in the setpoint as the valve changes from CLOSED state to OPEN state. R/W Float 2048
travel_rate_dec 400B Travel Rate CLOSE Describes the percentage of change per second in the setpoint as the valve changes from OPEN state to CLOSED state. R/W Float 2048
calib_command 4AE0 Calibration Command Starts or cancels auto travel calibration and tuning. 0 = start auto cal., 1 = start tuning, 2 = start auto cal. and tuning, 240 = cancel auto cal. or tuning. W Unsigned 2048
prscnt_data_block_number 4D61 Block number See ND9100H(T) HART Field Device Specification for details. W Unsigned 4096
prscnt_data_item_selector 4D62 Item selector See ND9100H(T) HART Field Device Specification for details. W Unsigned 4096
parameter_number 4AE2 Parameter Number 16-bit integer defining Parameter Number in Database. R/W Unsigned 4096
parameter_type 4AE3 Parameter Type Parameter Type, 1 = integer, 2 = floating point. R/W Enum 4096
Name ID Label Description Type Access Class