Name ID Label Description Type Access Class
local_test_time_97 48FE W Float 4096
local_test_time_98 48FF W Float 4096
local_test_time_99 4900 W Float 4096
dev_var_code 4AD1 R/W Unsigned 4096
signal_dir 4007 Direction Defines the opening and closing direction of the valve with raising current loop signal. Options for this parameter are: ·Open: Rising Setpoint to Open ·Close: Rising Setpoint to Close R/W Enum 2048
characterization_type 4010 Characterization Type Flow Modification allows you to modify the flow characteristics curve of a valve to improve controllability of the valve and optimise control loop performance. Options for this parameter are: ·Linear (not used) ·Shape Factor ·Custom Table R/W Enum 2048
characterization_polynom_factor 4011 Shape Factor Shape Factor describes the nearest approximate or the exact shape of the valve characterization transfer function based on the following hyperbolic function: f(x) = x/(S+x(1-S)), where ·S = Shape Factor ·x = normalized (0-100%) Setpoint value ·f(x) = an intermediate calculation of the Target Position. R/W Float 2048
alt_char_polynom_factor 40AE R Float 2048
characterization_table_code 4AD2 Table Code R Unsigned 2048
cut_off_low 400C Low Cut-Off When this value is exceeded, the valve is forced to a 0% position. This is called the tight cut-off feature. If, for example, the value is 2%, tight shut-off starts when the input signal goes below 2%. R/W Float 2048