Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
local_test_time_97 | 48FE | W | Float | 4096 | ||
local_test_time_98 | 48FF | W | Float | 4096 | ||
local_test_time_99 | 4900 | W | Float | 4096 | ||
dev_var_code | 4AD1 | R/W | Unsigned | 4096 | ||
signal_dir | 4007 | Direction | Defines the opening and closing direction of the valve with raising current loop signal. Options for this parameter are: ·Open: Rising Setpoint to Open ·Close: Rising Setpoint to Close | R/W | Enum | 2048 |
characterization_type | 4010 | Characterization Type | Flow Modification allows you to modify the flow characteristics curve of a valve to improve controllability of the valve and optimise control loop performance. Options for this parameter are: ·Linear (not used) ·Shape Factor ·Custom Table | R/W | Enum | 2048 |
characterization_polynom_factor | 4011 | Shape Factor | Shape Factor describes the nearest approximate or the exact shape of the valve characterization transfer function based on the following hyperbolic function: f(x) = x/(S+x(1-S)), where ·S = Shape Factor ·x = normalized (0-100%) Setpoint value ·f(x) = an intermediate calculation of the Target Position. | R/W | Float | 2048 |
alt_char_polynom_factor | 40AE | R | Float | 2048 | ||
characterization_table_code | 4AD2 | Table Code | R | Unsigned | 2048 | |
cut_off_low | 400C | Low Cut-Off | When this value is exceeded, the valve is forced to a 0% position. This is called the tight cut-off feature. If, for example, the value is 2%, tight shut-off starts when the input signal goes below 2%. | R/W | Float | 2048 |
Name | ID | Label | Description | Type | Access | Class |