Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
primary_measure_upper_range_value | 4020 | URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
primary_measure_lower_range_value | 4021 | LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
primary_measure_damping_value | 4015 | PV Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 8 |
sensor_serial_number | 4022 | Snsr S/N | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R/W | Integer | 2048 |
reference_temp_digital_units | 4023 | RJC units | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R | Enum | 8 |
reference_temp_digital_value | 4024 | Term. Temp | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R/W | Float | 10 |
rRunningAverageFilter | 4028 | Running Average | Sensor running average filter settings: 1 to 16. A higher setting provides smoother input transitions, a lower setting provides a faster response time. | R/W | Integer | 8 |
rSensorUpperRange | 4006 | Sensor URV | The sensor input configuration upper range value | R/W | Float | 8 |
rSensorLowerRange | 4004 | Sensor LRV | The sensor input configuration lower range value | R/W | Float | 8 |
cMeasurementMode | 4029 | Measure Mode | The input type e.g. thermocouple, RTD, mV | R/W | Enum | 32 |
Name | ID | Label | Description | Type | Access | Class |