Loading…
Name ID Label Description Type Access Class
cMeasurementMode 402A Measure Mode The input type e.g. thermocouple, RTD, mV R/W Enum 32
cSensorTypeCode 402C Input Type Sensor variant type e.g. Pt3850, Pt3912 R/W Enum 2048
cInputFilter 402D Filter Sensor input filter frequency. This filter is designed to reduce the effects of mainsinduced noise. The value should be set to the frequency of the local AC supply- either 50Hz or 60Hz. R/W Enum 512
wOutputZero 4007 Out Zero Lower range output current value: 3.6 to 23.6 mA R/W Float 64
wOutputFull 4008 Out Full Upper range output current value: 3.6 to 23.6 mA R/W Float 64
cResetParameter 402E R/W Enum 8
BrokenWireDetection 402F Broken Wire Enable / disable broken wire detection R/W Enum 8
BrokenWireLevel 4030 Broken Wire Level The current input value to defined Broken wire condition, must be: >0 and R/W Float 8
cSmartRangeSelection 4000 Smart Range Selection User selects PV, input scaling, or custom linearization curve. R/W Enum 8
cNumberOfTrimmingPoints 4031 No. Trim Pts. Number of trimming points R/W Enum 8
Name ID Label Description Type Access Class