Loading…
Name ID Label Description Type Access Class
upperRange_value 00EA PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
lowerRange_value 00EB PV LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
current_date 1158 Current Date Current Date based upon the real-time clock in the field device R HartDate 2050
current_time 1159 Current Time Current Time based upon the real-time clock in the field device R Time 2050
last_clock_time 115B Set Clock Time Time to set the real time clock in the field device to, or time that the real-time clock was last set R/W Time 2048
last_clock_date 115A Set Clock Date Date to set the real-time clock in the field device to, or date that the real-time clock was last set R/W HartDate 2048
burst_message_number 12E7 Burst Message Number R/W Index 4096
update_period 12BE Update Period Update period for burst message R/W Time 2048
max_update_period 12BF Max Update Period Maxium update period for burst message R/W Time 2048
burst_variable_code 1263 Burst Variable Code Burst Variable Slot - Device variable code assigned to the slot to be read in burst mode. R/W Index 128
Name ID Label Description Type Access Class