Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
AO2maxUpperRange | 4036 | AO2 ORV | Analog output 2 over range maximum value (4.6 to 23.6 mA) | R/W | Float | 8 |
AO2minLowerRange | 4037 | AO2 URV | Analog output 2 under range minimum value (3.6 to 22.6 mA) | R/W | Float | 8 |
AO2SensorErrorCurrent | 4038 | Fail AO2 | Sensor error (fail mode) analog output 2 value (3.6 to 4.0 mA failed low or 20 to 23.6 mA failed high) | R/W | Float | 8 |
AO1_damping_rate | 400F | AO1 Damping Rate | AO1 Damping rate in second (0.0 to 60.0) | R/W | Float | 8 |
AO2_damping_rate | 4039 | AO2 Damping Rate | AO2 Damping rate in second (0.0 to 60.0) | R/W | Float | 8 |
reserved | 403A | R/W | Integer | 2048 | ||
primary_measure_sensor_units | 400B | EGU | Unidade de variável do dispositivo de campo- Unidade de engenharia para ser apresentada com a representação do valor digital, intervalo mínimo, valor da faixa superior, valor da faixa inferior, limite do sensor inferior, e limite do sensor superior | R | Enum | 8 |
primary_measure_digital_units | 4009 | EGU | Unidade de variável do dispositivo de campo- Unidade de engenharia para ser apresentada com a representação do valor digital, intervalo mínimo, valor da faixa superior, valor da faixa inferior, limite do sensor inferior, e limite do sensor superior | R/W | Enum | 8 |
primary_measure_digital_value | 400A | PV | Valor da variável do dispositivo de campo- Valor digital que altera a magnitude em relação ao tempo sem a intervenção do usuário | R/W | Float | 10 |
primary_measure_percent_range | 401A | % range | Porcentagem da faixa – Variável que segue a representação do valor digital em relação à faixa definida pelo valor da faixa inferior e valor da faixa superior, para modos de operação normal. As unidades dessa variável são sempre em porcentagem. | R | Float | 10 |
Name | ID | Label | Description | Type | Access | Class |