Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
analog_output_transfer_function | 401B | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |
analog_value | 4007 | AO1 | Analog Output- Measurable physical output which changes with respect to time, without user intervention | R/W | Float | 66 |
ao2_value | 402F | AO2 | Analog Output- Measurable physical output which changes with respect to time, without user intervention | R/W | Float | 66 |
fail_mode | 4008 | AO1 Fail Mode | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R/W | Enum | 64 |
AO2fail_mode | 4030 | AO2 Fail Mode | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R/W | Enum | 64 |
AO1_source | 4031 | AO1 Source | User selects PV/SV/TV as the source for AO1 | R/W | Enum | 64 |
AO2_source | 4032 | AO2 Source | User selects PV/SV/TV as the source for AO2 | R/W | Enum | 64 |
AOmaxUpperRange | 4033 | AO1 ORV | Analog output 1 over range maximum value (4.6 to 23.6 mA) | R/W | Float | 8 |
AOminLowerRange | 4034 | AO1 URV | Analog output 1 under range minimum value (3.6 to 22.6 mA) | R/W | Float | 8 |
AOSensorErrorCurrent | 4035 | Fail AO1 | Sensor error (fail mode) analog output 1 value (3.6 to 4.0 mA failed low or 20 to 23.6 mA failed high) | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |