Name ID Label Description Type Access Class
cSmartRangeSelection 4021 Smart Range Selection User selects PV, input scaling, or custom linearization curve. R/W Enum 8
cNumberOfTrimmingPoints 402F No. Trim Pts. Number of trimming points R/W Enum 8
cInputTrimming 4030 Input Trimming Enable / Disable Sensor input trimming R/W Enum 8
AOmaxUpperRange 4031 AO ORV Analog output over range maximum value (4.6 to 23.6 mA) R/W Float 8
AOminLowerRange 4032 AO URV Analog output under range minimum value (3.6 to 22.6 mA) R/W Float 8
AOSensorErrorCurrent 4033 Fail Mode AO Sensor error (fail mode) analog output value (3.6 to 4.0 mA failed low or 20 to 23.6 mA failed high) R/W Float 8
cMII_TypeCode 4026 Model R Enum 2048
cScratchUnits 4034 R/W Enum 4096
UnknownByte 4035 R Integer 2048
transmitter_variable_trim_code 4047 Device Variable Trim Code- An index that identifies a Field Device Variable that supports the trim procedure R/W Index 4096