Loading…
Loading…
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
KDGM_pulse_repetition_rate | 4040 | Pulse Rate P041 | Pulse Rate - the interval between two ultrasonic transmit cycles may be set to, say, avoid crosstalk between two adjacent transmitters. The setting is typically 1.0 second. | 读/写 | 枚举 | 8 |
KDGM_echoes_needed | 4041 | Echoes Needed P042 | Echoes Needed - the number of echoes which must be returned from the same target before it is considered to be a valid target. The setting is typically 4 echoes. | 读/写 | 无符号 | 8 |
KDGM_target_threshold_1_time | 4085 | Threshold 1 Time P043 | Threshold 1 Time - the threshold may be set to an initial higher level set by P048. Threshold 1 Time sets the duration in milliseconds of that higher threshold. Note that 6 milliseconds is typically equivalent to a distance of 1 metre. | 读/写 | 浮点 | 8 |
KDGM_target_number_of_pulses | 4042 | Target Pulses P044 | Number of pulses - the number of cycles in the transmitted ultrasonic burst. The typical value is 10 cycles. | 读/写 | 枚举 | 8 |
KDGM_target_frequency_value | 402A | Target Frequency P045 | Target frequency - if set to Automatic the transmitter selects the best frequency for the application. It can be fixed, typically in the range of 48 to 58kHz. Not all integer values are available. | 读/写 | 枚举 | 8 |
SM_spike_rejection | 4047 | Spike Reject P049 | Spike Reject - rejects narrow echoes. Increasing P049 increases the width of rejected echoes. The typical value is 0 - i.e. no spike rejection | 读/写 | 无符号 | 8 |
SM_auto_cycle | 404D | Simulation Mode | Simulation Mode - the transmitter can simulate the level ramping between minimum and maximum. A complete cycle takes approximately 100 seconds. Auto-cycling may be paused. | 读/写 | 枚举 | 1024 |
SM_base_units | 402D | Base Units | Base Units - the transmitter can operate using Base Units of metres, feet or inches. Changing the Base Units will RESET the transmitter and restore it to ex-factory settings in the selected Base Units. | 读/写 | 枚举 | 2048 |
MOB_target_threshold_1_size | 40BD | Threshold 1 Size P048 | Threshold 1 Size - the amplitude of the initial high threshold. The duration is set by P043. | 读/写 | 浮点 | 8 |
MOB_transmit_power_control | 40BE | Power Control P040 | Transmit Power Control - if enabled then the transmitter automatically adjusts the transmitted pulse energy for optimum accuracy. | 读/写 | 枚举 | 1024 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |