Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
KDGM_speed_of_sound_reading | 401E | Speed of Sound D914 | Speed of sound - The speed of sound calculated from P024 and the temperature. | R | Float | 11 |
KDGM_temperature_reading | 4020 | Temperature for Calculation D915 | Temperature used for Speed of Sound Calculation - either the value preset in P025 or the value derived from the sensor in the transmitter. | R | Float | 11 |
SM_relay_status | 4027 | Relay Status D908 | Relay Status - The status of the transmitter relay contacts. | R | Enum | 1027 |
relay_nr | 404F | R/W | Index | 4096 | ||
SM_relay1_mode | 4051 | Mode 1 P070 | Mode 1 - the mode of operation of Relay 1. It may be On, Off or Setpoint. | R/W | Enum | 1024 |
SM_relay1_on_point | 4054 | On Point 1 P071 | On Point 1 - the value of Primary Variable beyond which Relay 1 contact is closed. | R/W | Float | 1024 |
SM_relay1_off_point | 4057 | Off Point 1 P072 | Off Point 1 - the value of Primary Variable beyond which Relay 1 contact is open. | R/W | Float | 1024 |
SM_relay2_mode | 4052 | Mode 2 P073 | Mode 2 - the mode of operation of Relay 2. It may be On, Off or Normal. If set to Normal and P074 and P075 are both 0.0, then Relay 2 acts as a Fault relay. | R/W | Enum | 1024 |
SM_relay2_on_point | 4055 | On Point 2 P074 | On Point 2 - the value of Primary Variable beyond which Relay 2 contact is closed. | R/W | Float | 1024 |
SM_relay2_off_point | 4058 | Off Point 2 P075 | Off Point 2 - the value of Primary Variable beyond which Relay 2 contact is open. | R/W | Float | 1024 |