名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
KDGM_plot_point_9 | 403E | Profile Pt.9 P038 | 90% height - The output in percent at 90% of the non linear profile height | 读/写 | 浮点 | 32 |
KDGM_plot_point_10 | 403F | Profile Pt.10 P039 | 100% height - The output in percent at 100% of the non linear profile height | 读/写 | 浮点 | 32 |
KDGM_pulse_repetition_rate | 4040 | Pulse Rate P041 | Pulse rate - The interval between two ultrasonic pulses may be changed to avoid crosstalk between two adjacent transmitters. The typical value is 1.0 second | 读/写 | 枚举 | 8 |
KDGM_echoes_needed | 4041 | Echoes Needed P042 | Echoes needed - The number of echoes which must be returned from the same target before it is considered to be a valid target. The value is typically 4 echoes | 读/写 | 无符号 | 8 |
KDGM_target_number_of_pulses | 4042 | Target Pulses P044 | Target Pulses P044 No of pulses - The number of cycles in the ultrasonic burst. The typical value is 10 cycles | 读/写 | 枚举 | 8 |
KDGM_target_frequency_value | 402A | Target Freq P045 | Target frequency - If set to Automatic the transmitter selects the best frequency for the application. It can be fixed, typically in the range of 48 to 58kHz. Not all integer values are available | 读/写 | 枚举 | 8 |
KDGM_temperature_max | 4043 | Max Temp P046 | Temperature max - The maximum temperature to which the transducer has been subjected | 读/写 | 整型 | 2049 |
KDGM_temperature_min | 4046 | Min Temp P047 | Temperature min - The minimum temperature to which the transducer has been subjected | 读/写 | 整型 | 2049 |
SM_spike_rejection | 4047 | Spike Reject P049 | Spike Reject - Reject narrow echoes. Increasing P049 increases the width of echoes rejected. The typical value is 0 .i.e NO spike rejection | 读/写 | 无符号 | 8 |
level_sensor_serial_number | 4009 | Sensor ser No P005 | Sensor serial number - Usually set to the same value as the Unique ID but may be changed for site use | 读/写 | 无符号 | 2048 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |