Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
temperature_value | 4013 | Xducer Temp D903 | Temperature - The value derived from the sensor in the transducer or connected externally (if fitted) | R | Float | 34 |
temperature_value_unit | 4012 | Temperature units | tvu | R | Enum | 2048 |
current_output | 4006 | Current output D906 | Current output - The analog value related to the PV | R | Float | 66 |
percent_range | 4007 | % Current Out D905 | Porcentaje de rango: Variable que rastrea la representación del valor digital con respecto al rango definido por el valor de rango inferior y el valor de rango superior, para modos de funcionamiento normales. Las unidades de esta variable siempre son en porcentaje. | R | Float | 34 |
SM_relay_status | 4027 | Relay Status D908 | Relay Status - The status of the transmitter relay contacts. 1 = Closed, 0 = Open | R | Enum | 34 |
level_damping_value | 4008 | Damping P020 | Smoothing time - The damping in seconds applied to the PV value and the analogue output | R/W | Float | 1024 |
KDGM_lost_echo_delay | 4030 | LE Delay P021 | Lost echo delay - The delay after which a continuous lost echo is reported, and the action specified by P022 taken | R/W | Float | 64 |
KDGM_lost_echo_action | 4031 | LE Action P022 | Lost echo action - The value to which the PV and current will be set, if the echo is lost for the time set by P021 | R/W | Enum | 64 |
KDGM_target_blanking_distance | 4032 | Blanking P023 | Blanking distance - The distance from the sensor up to which all echoes will be ignored | R/W | Float | 8 |
KDGM_speed_of_sound | 4033 | Speed of sound P024 | Speed of sound - The nominal speed of sound for the ullage space at 0øC | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |