Name ID Label Description Type Access Class
analog_value 4033 AO1 Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes R/W Float 66
input_percent_range 4034 PV % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
input_transfer_function 4035 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R/W Enum 32
sensor_serial_number 403A PV Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R/W Unsigned 2048
sensor_damping_value 4007 Damping Value Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 32
level_value 40E4 Level Level - Distance from bottom of tank to top of product. R Float 34
level_units 40E5 Level Unit Level transmitter units R/W Enum 2048
level_usl 40E6 Level USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 16
level_lsl 40E7 Level LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 16
level_min_span 40E8 Level Min Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 16
Name ID Label Description Type Access Class