Name ID Label Description Type Access Class
compensationStatus 4015 Temp Dev Stat R BitEnum 2
compensationUSL 4016 Temp USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 0
compensationLSL 4017 Temp LSL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 0
compensationMinimumSpan 4018 Temp min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 0
compensationDampingValue 4019 Temp damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R Float 0
compensationUpdatePeriod 401A Temp Update Period R Time 0
compensationSerialNumber 401B Temp snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R Unsigned 0
compensationSimulated 401C Simulate W Enum 0
SensorType 401E Sensor Type R/W Enum 3
SensorWireCheck 401F Sensor Wire Check R Enum 3
Name ID Label Description Type Access Class