Name ID Label Description Type Access Class
rt_zero 405F Zero Value A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. R/W Float 10
rt_sigma 4061 Standard Deviation A unitless value which characterizes the amount of deviation between readings during an Auto Zero operation. R Float 10
fault_index 4063 Output Type R/W Index 4096
LMV_fault_timeout 4067 Fault Timeout This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. R/W Unsigned 12
ao_1_fault_code 446D Fault Action Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. R/W Enum 12
ao_2_fault_code 456A Fault Action Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. R/W Enum 12
fo_fault_code 43A0 Fault Action Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. R/W Enum 12
dig_comm_fault_code 4594 Digital Fault Actions This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) R/W Enum 12
ao_1_fault_level 4566 Fault Level This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 1.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. R/W Float 64
ao_2_fault_level 456B Fault Level This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 1.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. R/W Float 64