Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
ao_1_fault_code | 4141 | Fault Action | Downscale: mA outputs that indicate flow go to the configured limit,the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. | R/W | Enum | 12 |
ao_2_fault_code | 4145 | Fault Action | Downscale: mA outputs that indicate flow go to the configured limit,the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. | R/W | Enum | 12 |
fo_fault_code | 4147 | Fault Action | Downscale: mA outputs that indicate flow go to the configured limit,the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. | R/W | Enum | 12 |
dig_comm_fault_code | 4149 | Fault Action | This fault setting applies to Modbus on RS485 and the display. Downscale: Hold process variables at values that are less than the Lower Sensor Limits and stop totalizing. Upscale: Hold process variables at values that are greater than the Upper Sensor Limits and stop totalizing. Not-a-Number: Set all process variables to IEEE NaN. IntZero-All 0: Set all process variables to 0. IntZero-Flow 0: Set flow rate to 0. None: Process variables displayed as measured (NOTE: Use alternative method to detect fault conditions when NONE is selected) | R/W | Enum | 12 |
ao_1_fault_level | 4143 | Fault Level | This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 1.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. | R/W | Float | 64 |
ao_2_fault_level | 4146 | Fault Level | This parameter allows you to select the lower or upper mA output level that will indicate a fault condition. The range is 1.0 to 3.6 mA for downscale or 21.0 to 24.0 for upscale. | R/W | Float | 64 |
fo_fault_level | 4148 | Fault Level | This parameter allows you to select the upper frequency output level that will indicate a fault condition. The maximum value is 15000 Hz. | R/W | Float | 64 |
ma_1_cutoff | 402D | mA Output Flow Rate Cutoff | The mass or volume flow rate below which is a mA output representing flow indicates zero flow. | R/W | Float | 8 |
ma_2_cutoff | 402F | mA Output Flow Rate Cutoff | The mass or volume flow rate below which is a mA output representing flow indicates zero flow. | R/W | Float | 8 |
cutoff_code | 414E | Cutoff Type | R/W | Index | 4096 | |
Name | ID | Label | Description | Type | Access | Class |