Name ID Label Description Type Access Class
fi_flow_rate_factor 4132 Rate Factor The flow rate that equals a set frequency if the frequency input represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency input represents mass or volume total. R/W Float 512
fi_pulsesPerUnit 4133 Pulses/Unit This parameter allows you to scale the frequency input in terms of the number of pulses per unit of flow. R/W Float 512
fi_unitsPerPulse 4134 Units/Pulse This parameter allows you to scale the frequency input in terms of the number of units of flow required to generate one pulse. R/W Float 512
fi_k_factor 4135 K Factor The number of frequency pulses per unit of flow that the frequency is inputting. For example 10 pulses/kg. R/W Float 512
max_zero 4136 Zero Time The amount of time the transmitter takes to determine its zero-flow reference point. The default zero time is 20 seconds. R/W Unsigned 12
rt_zero 4137 Zero Value A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. R/W Float 10
zero_offset_units 4138 Zero units Units for zero offset - always microseconds. R/W Unsigned 32
rt_sigma 4139 Standard Deviation A unitless value which characterizes the amount of deviation between readings during an Auto Zero operation. R Float 10
fault_index 413A Output Type R/W Index 4096
LMV_fault_timeout 413C Время задержки в случае неисправности This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. R/W Unsigned 12