Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
gas_vol_flow_digital_units | 44E5 | Gas Vol flo unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. | R/W | Enum | 32 |
gas_vol_flow_digital_value | 44E6 | Gas Vol flo | R | Float | 10 | |
gas_vol_flow_digital_cutoff | 44E7 | Gas Vol flo Cutoff | The volume flow rate below which the frequency/pulse output indicates zero flow, and below which totalizers stop counting. | R/W | Float | 8 |
gas_vol_flow_analog_value | 44E8 | Gas Vol flo | R/W | Float | 66 | |
gas_vol_flow_analog_upper_limit | 44E9 | Anlog upr limit | Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
gas_vol_flow_analog_lower_limit | 44EA | Anlog lor limit | Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
gas_vol_flow_additional_analog_damping | 44EB | Added damp | Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
gas_vol_flow_percent_range | 44EC | Vol flo % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
gas_vol_flow_upper_range_value | 44ED | Vol flo URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
gas_vol_flow_lower_range_value | 44EE | Vol flo LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
Name | ID | Label | Description | Type | Access | Class |