Name ID Label Description Type Access Class
fi_input_freq_digital_units 4650 FI Freq The frequency, in Hertz, presently being indicated on the frequency input. R Enum 32
fi_input_frequency 412E FI Freq R Unsigned 514
fi_scaling_method 412F FI Scale Method This parameter allows you to scale the frequency input by using freq=flow, pulses/unit, or units/pulse. This parameter must be sent to the device before you make scaling changes. R/W Enum 512
fi_freq_factor 4131 Freq factr The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency input. R/W Float 512
fi_flow_rate_factor 4132 Rate factr The flow rate that equals a set frequency if the frequency input represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency input represents mass or volume total. R/W Float 512
fi_pulsesPerUnit 4133 Pulses/Unit This parameter allows you to scale the frequency input in terms of the number of pulses per unit of flow. R/W Float 512
fi_unitsPerPulse 4134 Units/Pulse This parameter allows you to scale the frequency input in terms of the number of units of flow required to generate one pulse. R/W Float 512
fi_k_factor 4135 K Factor The number of frequency pulses per unit of flow that the frequency is inputting. For example 10 pulses/kg. R/W Float 512
max_zero 4136 Zero time The amount of time the transmitter takes to determine its zero-flow reference point. The default zero time is 20 seconds. R/W Unsigned 12
rt_zero 4137 Zero A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. R/W Float 10
Name ID Label Description Type Access Class