Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
mass_flow_digital_cutoff | 4013 | Mass flo cutoff | The mass flow rate below which the frequency/pulse output indicates zero flow, and below which totalizers stop counting. Cutoffs can also be configured for the mA output(s) (the AO cutoffs). An AO cutoff is active only if the process variable assigned to the output is mass flow or volume flow. | R/W | Float | 8 |
mass_flow_analog_value | 4014 | Mass flo anlog valu | R/W | Float | 66 | |
mass_flow_analog_value_1 | 4015 | Mass flo anlog valu | R/W | Float | 66 | |
mass_flow_analog_upper_limit | 4016 | Límite sup. analóg. | Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
mass_flow_analog_lower_limit | 4017 | Límite inf. analóg. | Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions | R | Float | 64 |
mass_flow_additional_analog_damping | 4018 | Added damp | Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
mass_flow_additional_analog_damping_1 | 4019 | Added damp | Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. | R/W | Float | 32 |
mass_flow_percent_range | 401A | Mass flo % rnge | Porcentaje de rango: Variable que rastrea la representación del valor digital con respecto al rango definido por el valor de rango inferior y el valor de rango superior, para modos de funcionamiento normales. Las unidades de esta variable siempre son en porcentaje. | R | Float | 34 |
mass_flow_percent_range_1 | 401B | Mass flo % rnge | Porcentaje de rango: Variable que rastrea la representación del valor digital con respecto al rango definido por el valor de rango inferior y el valor de rango superior, para modos de funcionamiento normales. Las unidades de esta variable siempre son en porcentaje. | R | Float | 34 |
alarm_select | 401C | AO Alrm typ | Determines whether the Event is activated when it goes above (High) or below (Low) the setpoint. | R | Enum | 10 |
Name | ID | Label | Description | Type | Access | Class |