Loading…
Name ID Label Description Type Access Class
live_zero_vol_flow_lower_range_value_1 450D Mass flo LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
live_zero_vol_flow_upper_sensor_limit 450E Mass flo URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
live_zero_vol_flow_lower_sensor_limit 450F Mass flo LRL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
live_zero_vol_flow_minimum_span 4510 Mass flo min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
live_zero_vol_flow_hzfreq 4511 Freq factr The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. R/W Float 512
live_zero_vol_flow_hzrate 4512 Rate factr The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. R/W Float 512
live_zero_vol_flow_p_u 4513 Pulses/Unit This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. R/W Float 512
live_zero_vol_flow_u_p 4514 Units/Pulse This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. R/W Float 512
Update_Period 4515 Update Period The period in which the process variables on the local display are updated. (in msec) R/W Unsigned 256
Language 4516 Display Language Current display language R/W Enum 256
Name ID Label Description Type Access Class