Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
flow_tgco | 40BB | FTG | This parameter represents the Flow Temperature Gradient Coefficient (FTG) that is on the T-series sensor tag. | R/W | Float | 8 |
flow_fqco | 40BC | FFQ | This parameter represents the Flow Frequency Coefficient (FFQ) that is on the T-series sensor tag. | R/W | Float | 8 |
max_zero | 40BD | Zero Time | The amount of time the transmitter takes to determine its zero-flow reference point. The default zero time is 20 seconds. | R/W | Unsigned | 12 |
pulse_width | 40BE | Maximum Pulse Width | A programmable time period, in seconds, that defines the crossover frequency for the frequency output, where Crossover freq. = 1 / (2 x Pulse width). Below the crossover, the output has a constant ON state, and an OFF state that varies with frequency. | R/W | Float | 512 |
tempcal | 40BF | Temperature Calibration Factor | A 14-character factor that describes the slope and offset of the linear output representing flow tube temperature. | R/W | ASCII | 32 |
rt_zero | 40C0 | Zero Value | A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. | R/W | Float | 10 |
zero_offset_units | 40C1 | Zero units | Units for zero offset - always microseconds. | R/W | Unsigned | 32 |
rt_sigma | 40C2 | Standard Deviation | A unitless value which characterizes the amount of deviation between readings during an Auto Zero operation. | R | Float | 10 |
fault_index | 40C3 | Output Type | R/W | Index | 4096 | |
LMV_fault_timeout | 40C5 | Fault Timeout | This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. | R/W | Unsigned | 12 |
Name | ID | Label | Description | Type | Access | Class |