Name ID Label Description Type Access Class
vol_flow_analog_value 4064 Volume Flow mA Value R/W Float 66
vol_flow_analog_upper_limit 4065 Anlog upr limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
vol_flow_analog_lower_limit 4066 Anlog lor limit Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
vol_flow_additional_analog_damping 4067 Added Damping Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
vol_flow_percent_range 4068 Volume Flow Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
vol_flow_upper_range_value 4069 Volume Flow Upper Range Value Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_lower_range_value 406A Volume Flow Lower Range Value Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_analog_value_1 406B Volume Flow mA Value R/W Float 66
vol_flow_additional_analog_damping_1 406C Added Damping Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
vol_flow_percent_range_1 406D Volume Flow Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
Name ID Label Description Type Access Class