Name ID Label Description Type Access Class
mass_flow_upper_sensor_limit 400C Mass Flow Upper Sensor Limit Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
mass_flow_lower_sensor_limit 401F Mass Flow Lower Sensor Limit Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
mass_flow_minimum_span 4020 Mass Flow Minimum Span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
mass_flow_hzfreq 4021 Frequency Factor The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. R/W Float 512
mass_flow_hzrate 4023 Rate Factor The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. R/W Float 512
mass_flow_p_u 4024 Pulses/Unit This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. R/W Float 512
mass_flow_u_p 4025 Units/Pulse This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. R/W Float 512
temp_digital_units 4031 Temperature Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R/W Enum 32
temp_digital_value 4032 Temperature R Float 10
temp_analog_value 4033 Temperature mA Value R/W Float 66