Name ID Label Description Type Access Class
live_zero 4100 Live zero flow This flow value is not effected by the flow cutoff and is damped at 8 seconds. It is to be used for diagnostic purposes only and is not used in ANY flow calculations or totalization. R Float 10
board_temp_700 4101 Board Temperature The board temperature of the core processor. R Float 10
case_temp 4102 Meter Temp: T-Series The meter temperature of the T-Series sensor. R Float 10
FD 4103 FD A calibration constant generated during a flowing density calibration. R/W Float 8
tot_reset 4104 Disp. Total Reset When this parameter is enabled, you can use the display to reset the totalizer. R/W Enum 256
auto_scroll 4105 Disp. Auto Scroll When this parameter is enabled, you do not need to press the scroll button to scroll through the configured process variables. R/W Enum 256
auto_scroll_rate 4106 Disp. scroll rate This parameter allows you to set the rate at which the display will scroll from one process variable to the next. Display Auto Scroll must be enabled. R/W Unsigned 256
offline_menu 4107 Disp. Offline Menu When this parameter is enabled, you can use the display to access the offline maintenance menu. R/W Enum 256
alarm_menu 4108 Disp. Alarm Menu When this parameter is enabled, you can use the display to acknowledge and view the specific alarm conditions that are present. When this parameter is disabled, all alarms will be automatically acknowledged without user intervention. R/W Enum 256
ack_all 4109 Disp. ACK All When this parameter is enabled, an option in the alarm menu allows you to acknowledge all of the alarms at once. R/W Enum 256