Name ID Label Description Type Access Class
vol_flow_upper_range_value 4069 Vol flo URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_lower_range_value 406A Vol flo LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_analog_value_1 406B Vol flo anlog valu R/W Float 66
vol_flow_additional_analog_damping_1 406C Added damp Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
vol_flow_percent_range_1 406D Vol flo % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
vol_flow_upper_range_value_1 406E Vol flo URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_lower_range_value_1 406F Vol flo LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_upper_sensor_limit 4062 Vol flo URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
vol_flow_lower_sensor_limit 4070 Vol flo LRL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
vol_flow_minimum_span 4071 Vol flo min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8