名称 ID 标签 描述 类型 访问 分类
mass_flow_upper_sensor_limit 400C 质量流量URL 传感器上限值——定义上限值的最大可用数值。 浮点 8
mass_flow_lower_sensor_limit 401F 质量流量LRL 传感器下限值——定义上限值的最小可用数值。 浮点 8
mass_flow_minimum_span 4020 质量流量最小范围 最小范围值——定义上限值和下限值之间允许的最小差。 浮点 8
mass_flow_hzfreq 4021 频率系数 The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. 读/写 浮点 512
mass_flow_hzrate 4023 速率系数 The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. 读/写 浮点 512
mass_flow_p_u 4024 Pulses/Unit This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. 读/写 浮点 512
mass_flow_u_p 4025 Units/Pulse This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. 读/写 浮点 512
temp_digital_units 4031 温度单位 Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. 读/写 枚举 32
temp_digital_value 4032 Temp 浮点 2
temp_analog_value 4033 温度模拟值 读/写 浮点 66