Name ID Label Description Type Access Class
vol_flow_lower_range_value_1 406F Vol flo LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
vol_flow_upper_sensor_limit 4062 Vol flo URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
vol_flow_lower_sensor_limit 4070 Vol flo LRL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
vol_flow_minimum_span 4071 Vol flo min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
vol_flow_hzfreq 4072 Freq factr The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. R/W Float 512
vol_flow_hzrate 4073 Rate factr The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. R/W Float 512
vol_flow_p_u 4074 Pulses/Unit This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. R/W Float 512
vol_flow_u_p 4075 Units/Pulse This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. R/W Float 512
vtot_digital_units 4078 Vol flo totl unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R Enum 32
vtot_digital_value 4079 Vol totl R Float 2
Name ID Label Description Type Access Class