Name ID Label Description Type Access Class
flow_fqco 40BC FFQ This parameter represents the Flow Frequency Coefficient (FFQ) that is on the T-series sensor tag. R/W Float 8
max_zero 40BD Zero time The number of readings collected from the sensor during an Auto Zero operation. R/W Unsigned 4
pulse_width 40BE Max pulse width A programmable time period, in seconds, that defines the crossover frequency for the frequency output, where Crossover freq. = 1 / (2 x Pulse width). Below the crossover, the output has a constant ON state, and an OFF state that varies with frequency. R/W Float 512
tempcal 40BF Temp cal factr A 14-character factor that describes the slope and offset of the linear output representing flow tube temperature. R/W ASCII 32
rt_zero 40C0 Zero A value, in microseconds, representing the phase shift between velocity signals from the sensor when measuring zero flow. R/W Float 2
zero_offset_units 40C1 Zero units Units for zero offset - always microseconds. R/W Unsigned 32
rt_sigma 40C2 Std dev A unitless value which characterizes the amount of deviation between readings during an Auto Zero operation. R Float 2
fault_index 40C3 Output Type R/W Index 4096
LMV_fault_timeout 40C5 Fault Timeout This parameter defines the number of seconds for which all outputs will hold their last measured value prior to going to the configured fault state. The default is zero seconds. R/W Unsigned 4
ao_1_fault_code 40CA AO1 Fault indicator Downscale: Milliamp outputs that indicate flow go to the configured limit, the frequency output equals 0 Hz. Upscale: Milliamp and frequency outputs go to the configured limit. Internal zero: Flow outputs indicate zero flow. R/W Enum 4
Name ID Label Description Type Access Class