Name ID Label Description Type Access Class
dens_lower_range_value_1 4058 Dens LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R/W Float 32
dens_upper_sensor_limit 404C Dens URL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
dens_digital_damping 4059 Dens damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R/W Float 32
dens_lower_sensor_limit 405A Dens LRL Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. R Float 8
dens_minimum_span 405B Dens min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
minv_digital_value 405E Mass inventory R Float 2
vol_flow_digital_units 4060 Vol flo unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R/W Enum 32
vol_flow_digital_value 4061 Vol flo R Float 2
vol_flow_digital_cutoff 4063 Vol flo cutoff The volume flow rate below which the frequency/pulse output indicates zero flow, and below which totalizers stop counting. R/W Float 8
vol_flow_analog_value 4064 Vol flo anlog valu R/W Float 66