Name ID Label Description Type Access Class
mass_flow_p_u 401D Pulses/Unit This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. R/W Float 512
mass_flow_u_p 401E Units/Pulse This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. R/W Float 512
temp_digital_units 4027 Temperature Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R/W Enum 32
temp_digital_value 4028 Temperature R Float 10
temp_analog_value 4029 Temperature mA Value R/W Float 66
temp_analog_value_1 4549 Temp anlog valu R/W Float 66
temp_analog_upper_limit 402A Anlog upr limit Analog Output Upper Endpoint Value- Defines the upper endpoint, of the respective Analog Output, for normal operating conditions R Float 64
temp_analog_lower_limit 402B Anlog lor limit Analog Output Lower Endpoint Value- Defines the lower endpoint, of the respective Analog Output, for normal operating conditions R Float 64
temp_additional_analog_damping 402C Added Damping Analog Output Added Damping Value- Damping time constant applied the Analog Output. The units of this variable are always in seconds. R/W Float 32
temp_percent_range 402D Temperature Percent Range Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34