Loading…
Name ID Label Description Type Access Class
vol_flow_hzfreq 4057 Frequency Factor The number of cycles, in Hertz, that equal a proportional flow rate represented by the frequency/pulse output. R/W Float 512
vol_flow_hzrate 4058 Rate Factor The flow rate that equals a set frequency if the frequency output represents mass or volume flow; or the mass or volume total that equals a set number of pulses if the frequency output represents mass or volume total. R/W Float 512
vol_flow_p_u 4059 Pulses/Unit This parameter allows you to scale the frequency output in terms of the number of pulses per unit of flow. R/W Float 512
vol_flow_u_p 405A Units/Pulse This parameter allows you to scale the frequency output in terms of the number of units of flow required to generate one pulse. R/W Float 512
vtot_digital_units 405C Vol flo totl unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. R Enum 32
vtot_digital_value 405D Volume Total R Float 10
vinv_digital_value 405F Volume Inventory R Float 10
pres_digital_units 41A0 Pressure Unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R/W Enum 32
pres_digital_value 4196 External Pressure R Float 10
pres_analog_value 41A2 AO R/W Float 66
Name ID Label Description Type Access Class